Manufacturer
OEM Part Number
GPS Part Number
Categories
Tags
$9,950.00
| Voltage | AH/kVA | Length | Width | Height | Weight |
|---|---|---|---|---|---|
| 15 kVA | 120/220 Vac | 33.5″ | 12.0″ | 32.2″ – 47.8″ | 381 – 587 lb |
| Voltage | 15Â kVA |
| Amp/H | 120/220Â Vac |
| Length | 33.5″ |
| Width | 12.0″ |
| Height | 32.2″ – 47.8″ |
| Weight | 381Â – 587Â lb |
Exact specifications for the Eaton/Powerware 9355 15Â kVA UPS (10/15Â kVA family), presented in our standard template and verified from the current OEM documentation.
| Category | Detail |
|---|---|
| Power & Topology | 15Â kVA / 13.5Â kW; online double-conversion; pure sine-wave output; Hot Syncâ„¢ parallel capable. |
| Input | Rated voltage: 120/208 or 127/220 Vac, 3-phase, 4-wire+G (single-feed). Operating freq.: 45–65 Hz (50/60-Hz auto-config). Voltage window (at 100% load, no battery discharge): −15% / +10% from nominal. Input PF: >0.99 (full load). Input current distortion: ≤5% THDi (active PFC). With optional input isolation transformer (60 Hz only): 480 V or 600 V ±20% input. Input current (by configuration): 208 V: 48 A • 480 V (with iso XFMR): 24 A • 600 V (with iso XFMR): 20 A • 220 V: 45.7 A. |
| Output | Nominal voltages: 120/208 or 127/220 Vac, 3-phase, 4-wire+G. Regulation: ±1% static (P-N), ±2% static (P-P); dynamic ±5% at 100% step, <1 ms response. Distortion: <2% THD (linear), <5% THD (non-linear). Output current (full load): 208-V L-L: 41.6 A • 220-V L-L: 39.4 A (identical 41.6 A listing shown across 208/480/600 input cases). |
| Bypass | Integrated static bypass (MBB wall-mount options available; input iso transformer cannot be used with wall-mount MBP). |
| Short-Circuit / AIC | Not specified in model tables; coordinate breaker ratings per site one-line. |
| Battery System | Internal VRLA, 9 Ah; nominal per string 192 Vdc (96 cells). Strings: UPS-32 (2 strings), UPS-64 (4 strings); max with EBMs: up to 22 strings total (UPS+EBMs). Charging: service-configurable 0.5–3.4 A/string (overall max 34 A); internal battery recharge ≈3 h to 80%. Typical full-load runtimes (mins): UPS-32: 4; UPS-64: 13; +EBM-64: 23/43/65/88 (1–4 cabs). |
| Controls & Comm | Backlit LCD; DB-9 serial; relay outputs & programmable inputs; REPO; optional X-Slot network (SNMP/web) & Modbus/RS-485 cards. |
| Physical | 2-High UPS: 32.2″ H Ă— 12.0″ W Ă— 33.5″ D; 381 lb. 3-High UPS-32: 47.8″ Ă— 12.0″ Ă— 33.5″; 587 lb • 3-High UPS-64: 47.8″ Ă— 12.0″ Ă— 33.5″; 619 lb. |
| Environment | Operating: 50–104 °F (10–40 °C); storage: 32–77 °F (0–25 °C) (transit −13–131 °F). RH: 5–95% non-condensing; altitude: up to 9843 ft (3000 m) without derating; acoustics: <56 dBA typical (<62 dBA heavy load/high ambient/on battery). |
| Accessory | Model | Notes |
|---|---|---|
| Extended Battery Module — 2-High | EBM-64 (103004192-5501) | 64 batteries; 32.2″ Ă— 12.0″ Ă— 30.3″; ≈480 lb. |
| Extended Battery Module — 3-High | EBM-96 (103004193-5501) | 96 batteries; 47.8″ Ă— 12.0″ Ă— 30.3″; ≈710 lb. |
| Wall-mount MBP Cabinet | (Version 1 / Version 2) | Make-before-break maintenance bypass (cannot be used with input iso transformer). |