Specifications
View Spec Sheet
Voltage AH/kVA Length Width Height Weight
15 kVA 120/220 Vac 33.5″ 12.0″  32.2″ – 47.8″ 381 – 587 lb
Voltage 15 kVA
Amp/H 120/220 Vac
Length 33.5″
Width 12.0″ 
Height 32.2″ – 47.8″
Weight 381 – 587 lb

Refurbished UPS — Eaton/Powerware (9355-15)

120/208 or 127/220 V, 3-phase (4-wire+G) •
Double-conversion (VFI) •
0.9 PF output (13.5 kW) •
Input PF >0.99 • Input THDi ≤5%

Exact specifications for the Eaton/Powerware 9355 15 kVA UPS (10/15 kVA family), presented in our standard template and verified from the current OEM documentation.

What you get
  • Thorough refurbishment — inspection, OEM-spec wear-part replacement, repaint, final QA
  • Comprehensive testing — burn-in, functional verification, alarm clear
  • Network-ready — serial/relay I/O standard; optional X-Slot cards (SNMP/web, Modbus)
  • Configured to order — 208/208 or 220/220 V, with optional 480/600-V input via isolation transformer
  • U.S. warranty & support from Gruber Power Services

Technical Specifications — 9355 15 kVA
Category Detail
Power & Topology 15 kVA / 13.5 kW; online double-conversion; pure sine-wave output; Hot Sync™ parallel capable.
Input Rated voltage: 120/208 or 127/220 Vac, 3-phase, 4-wire+G (single-feed).
Operating freq.: 45–65 Hz (50/60-Hz auto-config).
Voltage window (at 100% load, no battery discharge): −15% / +10% from nominal.
Input PF: >0.99 (full load). Input current distortion: ≤5% THDi (active PFC).
With optional input isolation transformer (60 Hz only): 480 V or 600 V ±20% input.
Input current (by configuration): 208 V: 48 A • 480 V (with iso XFMR): 24 A • 600 V (with iso XFMR): 20 A • 220 V: 45.7 A.
Output Nominal voltages: 120/208 or 127/220 Vac, 3-phase, 4-wire+G.
Regulation: ±1% static (P-N), ±2% static (P-P); dynamic ±5% at 100% step, <1 ms response.
Distortion: <2% THD (linear), <5% THD (non-linear).
Output current (full load): 208-V L-L: 41.6 A • 220-V L-L: 39.4 A (identical 41.6 A listing shown across 208/480/600 input cases).
Bypass Integrated static bypass (MBB wall-mount options available; input iso transformer cannot be used with wall-mount MBP).
Short-Circuit / AIC Not specified in model tables; coordinate breaker ratings per site one-line.
Battery System Internal VRLA, 9 Ah; nominal per string 192 Vdc (96 cells).
Strings: UPS-32 (2 strings), UPS-64 (4 strings); max with EBMs: up to 22 strings total (UPS+EBMs).
Charging: service-configurable 0.5–3.4 A/string (overall max 34 A); internal battery recharge ≈3 h to 80%.
Typical full-load runtimes (mins): UPS-32: 4; UPS-64: 13; +EBM-64: 23/43/65/88 (1–4 cabs).
Controls & Comm Backlit LCD; DB-9 serial; relay outputs & programmable inputs; REPO; optional X-Slot network (SNMP/web) & Modbus/RS-485 cards.
Physical 2-High UPS: 32.2″ H Ă— 12.0″ W Ă— 33.5″ D; 381 lb.
3-High UPS-32: 47.8″ Ă— 12.0″ Ă— 33.5″; 587 lb • 3-High UPS-64: 47.8″ Ă— 12.0″ Ă— 33.5″; 619 lb.
Environment Operating: 50–104 °F (10–40 °C); storage: 32–77 °F (0–25 °C) (transit −13–131 °F).
RH: 5–95% non-condensing; altitude: up to 9843 ft (3000 m) without derating; acoustics: <56 dBA typical (<62 dBA heavy load/high ambient/on battery).

Battery Cabinets & Options
Accessory Model Notes
Extended Battery Module — 2-High EBM-64 (103004192-5501) 64 batteries; 32.2″ Ă— 12.0″ Ă— 30.3″; ≈480 lb.
Extended Battery Module — 3-High EBM-96 (103004193-5501) 96 batteries; 47.8″ Ă— 12.0″ Ă— 30.3″; ≈710 lb.
Wall-mount MBP Cabinet (Version 1 / Version 2) Make-before-break maintenance bypass (cannot be used with input iso transformer).

Notes
  • All electrical and mechanical values above are taken from the 9355 10/15 kVA OEM user guide & datasheets for the exact 15 kVA model variants.
  • Use the optional input isolation transformer only where needed; it is incompatible with the wall-mount MBP.