Manufacturer
OEM Part Number
GPS Part Number
Categories
Tags
$17,357.00
Voltage | AH/kVA | Length | Width | Height | Weight |
---|---|---|---|---|---|
208/120 | 28.8 kVA | 36" | 24" | 81.1" | 1,276 lb |
Voltage | 208/120 |
Amp/H | 28.8 kVA |
Length | 36" |
Width | 24" |
Height | 81.1" |
Weight | 1,276 lb |
Designed to simplify power distribution without a raised floor, the InfraStruXure PDU integrates a 208โ208 V isolation transformer and a built-in maintenance bypass, providing flexible branch distribution for medium and large IT rooms. Our refurbished units are reconditioned, cosmetically refreshed to factory colors, and tested in the USA for reliable, ready-to-deploy service.
Category | Detail |
---|---|
Power & Architecture | 40 kW (โ 28.8 kVA) distribution PDU with integrated 208โ208 V isolation transformer; floor-standing cabinet |
Input | 208 V 3-phase (3ฮฆ), 60 Hz nominal |
Output | 208Y/120 V 3-phase distribution via branch circuits; typical receptacles include NEMA L21-20R (120/208 V, 20 A) and L6-30R (208 V, 30 A) as configured |
Bypass | Integrated maintenance bypass panel (MBP) for service without downtime |
Short-Circuit / AIC | โ (refer to site-specific upstream protection and breaker coordination) |
Monitoring & Alarms | Local alarm/monitoring; documentation and options available per configuration |
Receptacles (example) | NEMA L21-20R (qty varies), NEMA L6-30R (qty varies); branch breaker layout configurable |
Physical | โ 81.1โณ H ร 24โณ W ร 36โณ D; ~ 1,276 lb (cabinet with transformer) |
Environment | Indoor, data-center use; see OEM docs for detailed temperature/humidity limits |
Standards | UL / cUL compliance (per model family) |
Accessory | Model | Notes |
---|---|---|
Cable Extender Kit | PD Cable Extender | Installation accessory for PD40-series PDUs (see APC installation guide) |
Branch Circuit Options | โ | Varies by configuration (mix of L21-20R, L6-30R, and hard-wired panels) |
Monitoring / Comms | โ | Contact us for available metering/monitoring add-ons for this model family |