Voltage | AH/kVA | Length | Width | Height | Weight |
---|---|---|---|---|---|
60ย kW / 60ย kVA | 208ย VAC | 35.5โณ | 48.0โณ | 81.5โณ | 2,748ย lb |
Voltage | 60ย kW / 60ย kVA |
Amp/H | 208ย VAC |
Length | 35.5โณ |
Width | 48.0โณ |
Height | 81.5โณ |
Weight | 2,748ย lb |
Symmetraย PX 60ย kW brings modular, service-friendly protection with the option to scale to 80ย kW (N+1) using 10ย kW power
modules. Each unit is fully reconditioned, cosmetically refreshed, and tested in the USA for reliable, ready-to-deploy service.
Category | Detail |
---|---|
Power & Topology | 60ย kW / 60ย kVA; true double-conversion on-line; scalable with 10ย kW power modules to 80ย kW (N+1) |
Input | 208ย VAC 3-phase, 5-wire (3P+N+G); input window 177โ240ย VAC; frequency 40โ70ย Hz; input PF โ0.99 (full load); input THDi <5% (typ.) |
Output | 120/208ย VAC, 3-phase; regulation ยฑ1% (static), ยฑ5% @ 100% step; VTHD <2% (linear) / <6% (non-linear); nominal output current โ167ย A @ 60ย kW (ref.), 222ย A @ 80ย kW build |
Bypass | Integrated static bypass; wrap-around maintenance bypass via sidecar or site MBB panel |
Short-Circuit / AIC | Short-time withstand up to ~30ย kA on 208ย V PX frames (reference family spec) |
Battery System | Premium XR external battery enclosure(s); hot-swappable PX battery modules (SYBTU1-PLP); split DC bus ยฑ192ย V (โ384ย V nominal); typical recharge โ2ย h |
Controls & Comm | LCD/HMI with metering & event log; IntelliSlot network cards (SNMP/web), RS-485/Modbus, and dry-contact/relay options; EPO/REPO |
Physical | 81.5โณ H ร 48.0โณ W ร 35.5โณ D (2070 ร 1219 ร 902ย mm) lineup with Premium XR; product weight โ 2748ย lb |
Environment | Indoor, 0โ40ย ยฐC; โค95% RH non-condensing; install per OEM clearances/ventilation; altitude to ~1000ย m without derating (typ.) |
Accessory | Model | Notes |
---|---|---|
10ย kW Power Module | SYPM10KF / SYPM10KF2 | Hot-swappable PX power module (KF2 = high-efficiency successor) |
Battery Module | SYBTU1-PLP | PX hot-swap battery unit used in XR enclosures |
XR Battery Enclosure | SYCFXR9 (family) | External runtime expansion (rows of SYBTU1-PLP modules) |
Maintenance Bypass | MBB / BDC sidecar | Wrap-around service bypass & distribution options |