APC – AP7541 – Basic PDU – Tested

Manufacturer

OEM Part Number

AP7541

GPS Part Number

AP7541

Tags

Price:

$483.99

Specifications
View Spec Sheet
Voltage AH/kVA Length Width Height Weight
200 VAC 4,992 VA 63.74in 2.20in 1.73in 10.71-12.72lb
Voltage 200 VAC
Amp/H 4,992 VA
Length 63.74in
Width 2.20in
Height 1.73in
Weight 10.71-12.72lb

APC NetShelter — Basic Rack PDU (AP7541)

This is the Tested Version.

SKU: AP7541 |

Type: 0U vertical, Basic (non-metered) rack PDU for single-phase 200/208/230 V racks, 30 A input. Mixed IEC layout — 20 × C13 and 4 × C19 — on a 10 ft (3.05 m) line cord with NEMA L6-30P. Delivers up to 4,992 VA (line-rated 24 A).

  • Outlet mix: 20 × IEC 60320 C13 + 4 × IEC 60320 C19 (total 24).
  • Input: 200/208/230 V single-phase, NEMA L6-30P; 10 ft (3.05 m) cord; 50/60 Hz.
  • Current & capacity: Input limit 30 A; line-rated 24 A; 4,992 VA total.
  • Zero-U vertical: Preserves rack U-space; includes toolless mounting kit and brackets.
  • Data-center ready: UL/cUL listed, PSE/METI Denan; operating 32–113 °F (0–45 °C), 0–95% RH.

Technical Specifications — AP7541
Parameter Detail
PDU Type Basic; Zero-U vertical (0U)
Input 200/208/230 VAC; NEMA L6-30P; cord length 10 ft (3.05 m); 1 power cord
Current Input current limit 30 A; line-rated current 24 A
Output Voltage 200 V / 208 V
Outlets 20 × IEC 60320 C13  |  4 × IEC 60320 C19 (total 24)
Load Capacity 4,992 VA (nominal 5.0 kVA class)
Frequency 50/60 Hz
Dimensions (H×W×D) 63.74 × 2.20 × 1.73 in (1619 × 56 × 44 mm)
Net Weight 12.28 lb (5.57 kg)
Included Hardware Toolless mounting kit; rack mounting brackets; installation guide
Certifications UL Listed; cUL Listed; PSE; METI Denan
Standards UL 60950-1; CSA C22.2 No. 60950-1-03
Environment Operating: 32–113 °F (0–45 °C), 0–95% RH; Altitude 0–10,000 ft  |  Storage: −13–149 °F (−25–65 °C), 0–95% RH; Altitude 0–50,000 ft
Warranty (mfr.) 2-year repair or replace

Notes & Replacement

AP7541 is a current Zero-U Basic PDU (no local metering). If you need local/network metering, see AP8841 (0U, 30 A, 200/208 V, 36 × C13 + 6 × C19). For lower-amp Basic with L6-20P input, see AP7540 (20 A). For 230 V regions with a C20 inlet (16 A) or 32 A pin-&-sleeve, see AP7552 and AP7553 respectively.

Product Options — Tested vs. Refurbished PDUs
Option Description Warranty
Tested Operationally verified PDU. All IEC outlets checked under load; cord/plug inspected; continuity and ground confirmed. 90‑Day
Refurbished Cleaned and serviced PDU; cosmetic touch-ups as needed; outlets re-verified after service. 1‑Year

    • Use case: Straightforward 200/208/230 V distribution with mixed C13/C19 outlets; no network features.
    • Space: Zero-U mounting preserves 19″ rack units for gear.
    • Install tip: Balance C13/C19 loads; observe 24 A continuous (80% of 30 A) line rating.

Compatibility & Variants Matrix
Model Input / Plug Outlets Rating / Notes
AP7541 200/208/230 V 1φ / NEMA L6-30P; 10 ft cord 20 × C13; 4 × C19 Zero-U Basic; 30 A max (24 A line-rated); 4.992 kVA.
AP7540 208 V (some regions 200/230 V) / NEMA L6-20P; 10 ft cord 20 × C13; 4 × C19 Zero-U Basic; 20 A (≈3.3 kVA) lower-amp alternative.
AP7552 230 V 1φ / IEC C20 inlet; 10 ft cord 20 × C13; 4 × C19 Zero-U Basic; 16 A (EU/INTL C20 inlet variant).
AP7553 230 V 1φ / IEC 60309 32 A 2P+E 20 × C13; 4 × C19 Zero-U Basic; 32 A high-capacity international variant.

 

Why buy from Gruber
  • Professionally tested — All outlets verified under load; earth/continuity checks documented.
  • Exact fit hardware — Ships with the correct Zero-U mounting kit and brackets.
  • Fleet-ready — Mixed C13/C19 supports servers, blades, and network gear from one PDU.