APC – Galaxy VS – 20000 – 20 kVA – Three Phase Online UPS

Manufacturer

OEM Part Number

APC-GVSUPS20KB4HS

GPS Part Number

67-APC-GVSUPS20KB4HS

Price:

Specifications
Voltage WPC AH/kVA Length Width Height Weight
208VAC N/A 20 Kva 34" 21" 59" 706 lb
Voltage 208VAC
WPC N/A
Amp/H 20 Kva
Length 34"
Width 21"
Height 59"
Weight 706 lb
Galaxy VS UPS — 20 kW / 20 kVA, 400 V 3-Phase (1× 9Ah Smart Modular Battery String, Expandable to 4)

Highly efficient, easy-to-deploy 20 kW, 400 V three-phase UPS designed to deliver best-in-class power protection and low total cost of ownership for edge, small/medium data centers, and commercial & industrial critical loads. Ships with 1 internal 9Ah smart high-capacity modular battery string and supports expansion up to 4 strings for extended runtime (runtime charts available in the Documents tab).

Why these fail
  • Undersizing — growth planning is skipped, leading to overloads and nuisance transfers.
  • Poor power quality — high THD and unstable mains create heat, stress, and premature component aging.
  • Harsh short-circuit environments — installations exceed equipment withstand or bypass capability.
  • Inadequate commissioning — settings, sync modes, and bypass behavior aren’t validated under load.
Our solution
  • High efficiency + low distortion — input THD < 3% at full load; output THD < 1% (linear) / < 3% (non-linear).
  • Wide operating window — maintains efficiency from 340…460 V (400 V nominal range).
  • Built-in static bypass — robust continuity during fault/overload scenarios.
  • Scalable battery architecture — 1 string installed; expand to 4 strings when runtime demands increase.
  • Included 5×8 start-up — on-site commissioning support (5 days × 8 hours) to validate configuration and operation.
Category Detail
Rated Output 20 kW / 20 kVA
Input Voltage 380 / 400 / 415 V AC, 3-phase
Output Voltage 380 / 400 / 415 V AC, 3-phase
Frequency Input 40–70 Hz • Output 50/60 Hz (sync to mains) or 50/60 Hz ±0.1% (free-run)
Input Current (Max/Phase) 36 A
Short-Circuit Withstand (Icw) 65 kA
Power Factor / Cos φ Load PF 0.7 leading to 0.7 lagging (no derating) • Cos φ 0.99
Harmonics Input THD < 3% (full load) • Output THD < 1% linear / < 3% non-linear load
Bypass Built-in static bypass
Overload Capability 10 min @ 125% • 60 sec @ 150%
Waveform / Regulation Sine wave • Output voltage tolerance ±1% after 50 ms
Crest Factor 2.5
Wiring / Connectors Input: Hard-wire 4-wire (3PH + G) or 5-wire (3PH + N + G) •
Output: Hard-wire 5-wire (3PH + N + G)
Battery (Installed) 1× internal 9Ah smart modular battery string
Battery Expansion Expandable up to 4 strings total for increased runtime
Included Service 5×8 Start-Up (commissioning support during standard business hours)
💡
Maintenance tip: For best lifecycle performance, size the UPS for growth (headroom) and validate harmonic/load profile during commissioning—especially for non-linear IT loads.
🛠️
Tech support: Need help confirming 380/400/415 V site compatibility, bypass requirements, or battery string sizing? Email gps@gruber.com.