Products

Call Now For Support
1-800-658-5883

12 Volt – 135 Amp Hour YUASA Battery

Manufacturer

OEM Part Number

SWU500-12FR

GPS Part Number

58SSWU500-12FR

Categories

Price:

$400.00

Specifications
View Spec Sheet
Voltage AH/kVA Length Width Height Weight
12 Volt 135 AH 13.43" 6.81" 11.06" 97 lbs
Voltage 12 Volt
Amp/H 135 AH
Length 13.43"
Width 6.81"
Height 11.06"
Weight 97 lbs
12V 135Ah High-Temperature VRLA AGM Battery
HT X Alloy™ • 10-Year Design Life • UPS & Datacenter Standby Power

The Yuasa SWU500-12FR is a 12-volt, valve-regulated lead-acid (VRLA) battery using absorbed glass mat (AGM) technology
and Yuasa’s high-temperature HT X Alloy™ for extended life in demanding environments. Rated at
135 Ah (20-hr rate) and up to 500 W/cell at 15 minutes (1.67Vpc, 25°C), it delivers robust short-duration
ride-through and reliable long-term standby power for UPS systems, datacenters, switchgear, control, and other critical
infrastructure.

With a 10-year design life, flame-arresting one-way vent, and a flame-retardant UL94V-0 ABS case, the SWU500-12FR
is built for safety and durability in high-density installations. Epoxy-sealed terminals prevent post leaks and the
maintenance-free, non-spillable AGM design meets or exceeds DOT and IATA requirements for non-hazardous transportation.
Top-mounted M6 terminals simplify cabinet and rack installation, while certifications to ISO 9001, ISO 14001,
and IEC 60896-21
plus UL recognition ensure compliance with global quality and safety standards.

Key Features
  • 12V, 135 Ah (20-hr) VRLA AGM battery optimized for high-temperature standby use.
  • High discharge capability — 500 W/cell at 15 minutes (1.67Vpc, 25°C) for strong UPS ride-through performance.
  • 10-year design life with low self-discharge (~3% per month at 25°C) and rugged ABS case.
  • Flame-retardant construction — UL94V-0 case, flame-arresting one-way vent, and epoxy-sealed terminals.
  • Maintenance-free, non-spillable AGM design for flexible mounting in cabinets and racks.
  • Top M6 terminals with recommended torque of 4.9 Nm (43 in-lb) for secure connections.
  • Wide operating temperature — discharge from -20°C to 60°C (-4°F to 140°F); operating range -40°C to 65°C (-40°F to 149°F) per manual.
  • Complies with ISO 9001, ISO 14001, IEC 60896-21; UL recognized component (U1989); TAA compliant and DRC conflict-free.
Quick Specs
Parameter Value
Model SWU500-12FR
Nominal Voltage 12 V
Capacity 135 Ah (20-hr rate @ 1.75Vpc, 25°C)
15-min Power 500 W/cell @ 1.67Vpc, 25°C (77°F)
Short-Circuit Current 2975 A
Maximum Charge Current 34.0 A
Internal Resistance 3.2 mΩ
Dimensions (L × W × H) 341.0 × 173.0 × 281.0 mm (13.43″ × 6.81″ × 11.06″)
Weight 44.0 kg (97.0 lb)
Float Charge Voltage @ 25°C 2.275 ±1% V/cell (temperature compensation −3mV/°C per cell)
Design Life 10 years (standby use)
Typical Applications UPS, datacenter, switchgear & control, energy storage and backup power