$750.00
| Voltage | AH/kVA | Length | Width | Height | Weight |
|---|---|---|---|---|---|
| 690 V | 400 A | 4.1" | 5.5" | 8.1" | 11.2 lbs |
| Voltage | 690 V |
| Amp/H | 400 A |
| Length | 4.1" |
| Width | 5.5" |
| Height | 8.1" |
| Weight | 11.2 lbs |
Genuine ABB SACE Tmax T5N breaker professionally removed from a functioning system, then cleaned, inspected, and shop-tested. A fast, like-for-like replacement when uptime matters.
| Parameter | Detail |
|---|---|
| Manufacturer | ABB |
| Model / family | SACE Tmax T5N 400 โข 3-Pole โข Label code N5596 |
| Rated current (In) | 400ย A (T5N400 frame) |
| Trip unit type | Thermal-magnetic (TMA) |
| Rated operational voltage (Ue) | Up to 690ย Vย AC โข up to 750ย Vย DC (per variant) |
| Rated insulation / impulse (Ui / Uimp) | Uiย =ย 1000ย V โข Uimpย =ย 8ย kV |
| Interrupting / breaking capacity | IECย 60947-2: 70ย kA @ 220โ230ย Vย AC; 36ย kA @ 380/400/415ย Vย AC; 30ย kA @ 440ย Vย AC; 25ย kA @ 500ย Vย AC; 20ย kA @ 690ย Vย AC ULย 489 class โNโ: 65ย kA @ 240ย Vย AC; 25ย kA @ 480ย Vย AC; 14ย kA @ 600ย Vย AC |
| Poles | 3ย Poles |
| Terminations | Front terminals (FF), line & load |
| Mounting | Fixed, panel / switchgear |
| Dimensions (H ร W ร D) | 205ย mm ร 140ย mm ร 103.5ย mm (8.07ย in ร 5.51ย in ร 4.07ย in) |
| Weight | โย 5.1ย kg (โย 11.2ย lb) |
| Standards / approvals | IECย 60947-2; ULย 489 / CSAย C22.2 (as marked) |
| Condition | Tested pull โ cleaned, inspected, verified; light cosmetic wear only |
| Option | Whatโs included | Warranty |
|---|---|---|
| Tested Pull | Cleaned, inspected, verified operation; intact labels; ready to install | 90โDay |