Shop Products

Our Companies

Call Now For Support
1-800-658-5883

PRX – 143-22-002H – IGBT Power Transistor – Reclaimed Part

Manufacturer

OEM Part Number

143-22-002H

GPS Part Number

27-PRX-143-22-002H

Tags

Price:

$220.00

Specifications
Voltage WPC AH/kVA Length Width Height Weight
1600 V N/A 393 A N/A N/A N/A 1 kg
Voltage 1600 V
WPC N/A
Amp/H 393 A
Length N/A
Width N/A
Height N/A
Weight 1 kg

Powerex — 143-224-002H Thyristor Module
1600 V •
250 A ITAV •
Dual phase-control thyristors (inverse-parallel) •
Isolated POW-R-BLOKâ„¢ baseplate (ND43 class)
What it is

1.6 kV, 250 A dual SCR (phase-control) block used in soft-starts, controlled rectifiers, and UPS input bridges.
Isolated DCB base simplifies heatsinking; robust surge and dv/dt/di/dt handling for industrial AC control.

At-a-Glance
  • Voltage / Current: 1600 V / 250 A ITAV (≈ 393 A ITRMS)
  • Topology: Dual thyristor (inverse-parallel), phase-control
  • Mounting: Screw-mount, isolated baseplate (ND43 block)
  • Use Cases: Soft-starts; controlled rectifiers; AC regulators; UPS front-ends
  • Condition Options: NOS or tested reclaimed pulls
Features
  • High surge strength — ITSM 8.8 kA (1-cycle, 60 Hz).
  • Rugged dynamics — (di/dt)max 800 A/µs; minimum dV/dt 500 V/µs.
  • Low on-state model — VT0 ≈ 0.8 V; rT ≈ 0.68–1.5 mΩ (family values).
  • Isolated base — simplifies layout and grounding.
Technical Specifications
Parameter Value
Manufacturer Powerex
Part Number 143-224-002H
Device Type Dual phase-control thyristor module (inverse-parallel)
Repetitive Peak Off-State / Reverse Voltage (VDRM, VRRM) 1600 V
On-State Current, RMS (ITRMS) ≈ 393 A (180° sine)
Average On-State Current (per arm) ITAV = 250 A @ TC≈85–89 °C
Surge On-State Current ITSM = 8.8 kA (1-cycle, 60 Hz)
I²t (8.3 ms) ≈ 322 kA²·s
Critical dV/dt (min) 500 V/µs (gate open)
Critical di/dt (non-rep.) 800 A/µs
Gate Trigger / Holding IGT ≤ 150 mA; VGT ≤ 3.0 V; IH ≤ 150 mA
Thermal Resistance RθJC ≈ 0.14 °C/W (per junction); RθCS ≈ 0.03 °C/W (greased)
Isolation (baseplate) 2.5–3.6 kVRMS / 1 min (family)
Operating Junction Range −40 °C to +130 °C
Package / Footprint ND43 POW-R-BLOK™; ~116 × 50 × 55 mm; ≈ 0.84 kg; M8 power studs; keyed 2.8 mm control tabs
Configuration Dual (two SCRs, inverse-parallel)
Compatibility / Representative Uses
Module Applications Notes
143-224-002H (ND43 class) Soft-starts; controlled rectifiers; AC regulators; UPS input bridges Use ND43 mounting centers; observe surge and dv/dt/di/dt limits.
Why buy from Gruber
  • Tested pulls & new stock — Trigger behavior verified, continuity checked, base flatness inspected.
  • Traceability — Each module labeled with a work-order ID for service history confidence.
  • UPS expertise — We help match PRX customs to standard ND family blocks for drop-in replacements.
Gruber Power Services