APC – Galaxy VS – 30000 – 30 kVA – Three Phase Online UPS

Manufacturer

OEM Part Number

APC-GVSUPS30K0B5FS

GPS Part Number

67-APC-GVSUPS30K0B5FS

Price:

Specifications
Voltage WPC AH/kVA Length Width Height Weight
208VAC N/A 30 Kva 34" 21" 59" 706 lb
Voltage 208VAC
WPC N/A
Amp/H 30 Kva
Length 34"
Width 21"
Height 59"
Weight 706 lb
Galaxy VS UPS — 30 kW / 30 kVA, 208 V 3-Phase (Battery-Ready, Up to 5× 9Ah Smart Modular Strings)

Highly efficient, easy-to-deploy 30 kW, 208 V three-phase UPS delivering best-in-class power protection and low total cost of ownership for edge, small/medium data centers, and commercial & industrial critical loads. Designed for up to 5 internal 9Ah smart modular high-capacity battery strings (VRLA, 480 V system). Supplied without batteries so runtime can be fully customized to site requirements. Includes 5×8 start-up service.

Why these fail
  • Runtime miscalculation — battery strings are undersized for real-world load profiles.
  • High harmonic environments — excess THD increases heat and stresses rectifier/inverter stages.
  • Improper commissioning — sync modes and bypass settings not validated under load.
  • Short-circuit exposure — upstream fault levels exceed system withstand ratings.
Our solution
  • Scalable battery architecture — install 1–5 smart modular strings as runtime demands evolve.
  • Low distortion performance — input THD < 3% at full load; output THD < 1% (linear) / < 5% (non-linear).
  • Wide operating window — optimized efficiency from 177…239 V (208 V nominal).
  • Built-in static bypass — seamless transfer during overload or fault events.
  • Embedded network management — integrated Network Management Card 4, EcoStruxure™ ready.
Category Detail
Rated Output 30 kW / 30 kVA
Input Voltage 200 / 208 / 220 V AC, 3-phase
Output Voltage 200 / 208 / 220 V AC, 3-phase
Frequency Input 40–70 Hz • Output 50/60 Hz (sync to mains)
Input Current (Max/Phase) 107 A
Short-Circuit Withstand (Icw) 65 kA
Power Factor / Cos φ Load PF 0.7 leading to 0.7 lagging (no derating) • Cos φ 0.99
Harmonics Input THD < 3% • Output THD < 1% linear / < 5% non-linear
Bypass Built-in static bypass
Overload Capability 10 min @ 125% • 60 sec @ 150%
Battery System Internal modular VRLA • 480 V battery system • Up to 5 strings
End-of-discharge voltage: 384 V DC • Max discharge current: 81 A
Batteries sold separately
User Interface Touch Screen LCD
Connectivity Embedded Network Management Card 4 • EcoStruxure Ready
Dimensions (H×W×D) 77.6 × 21.7 × 33.3 in (197 × 55 × 84.7 cm)
Weight 586.4 lb (266 kg)
Included Equipment Dust filter • Installation manual • Integrated network management • 5×8 Start-Up Service
Service & coverage

5×8 start-up service ensures professional commissioning, configuration validation, and operational verification. Runtime is fully customizable based on the number of installed battery strings (0–5).

💡
Design tip: When configuring battery strings, confirm required runtime at actual load (kW), not nameplate kVA, to avoid undersizing.
🛠️
Tech support: Need help selecting the correct number of battery strings or confirming 200/208/220 V site compatibility? Email