APC – Galaxy VS – 10000 – 10 kVA – Three Phase Online UPS

Manufacturer

OEM Part Number

APC-GVSUPS10KB4HS

GPS Part Number

67-APC-GVSUPS10KB4HS

Price:

Call for Price

Specifications
View Spec Sheet
Voltage AH/kVA Length Width Height Weight
208VAC 10 Kva 34" 21" 59" 706ย lb
Voltage 208VAC
Amp/H 10 Kva
Length 34"
Width 21"
Height 59"
Weight 706ย lb
Galaxy VS UPS โ€” 10 kW / 10 kVA, 400 V 3-Phase (1ร— 9Ah Smart Modular Battery String, Expandable to 4)

Highly efficient, easy-to-deploy 10 kW, 400 V three-phase UPS designed to deliver best-in-class power protection and low total cost of ownership for edge, small/medium data centers, and commercial & industrial critical loads. Ships with 1 internal 9Ah smart high-capacity modular battery string and supports expansion up to 4 strings for extended runtime (runtime charts available in the Documents tab).

Why these fail
  • Undersizing โ€” growth planning is skipped, leading to overloads and nuisance transfers.
  • Poor power quality โ€” high THD and unstable mains create heat, stress, and premature component aging.
  • Harsh short-circuit environments โ€” installations exceed equipment withstand or bypass capability.
  • Inadequate commissioning โ€” settings, sync modes, and bypass behavior arenโ€™t validated under load.
Our solution
  • High efficiency + low distortion โ€” input THD < 3% at full load; output THD < 1% (linear) / < 3% (non-linear).
  • Wide operating window โ€” maintains efficiency from 340โ€ฆ460 V (400 V nominal range).
  • Built-in static bypass โ€” robust continuity during fault/overload scenarios.
  • Scalable battery architecture โ€” 1 string installed; expand to 4 strings when runtime demands increase.
  • Included 5ร—8 start-up โ€” on-site commissioning support (5 days ร— 8 hours) to validate configuration and operation.
Category Detail
Rated Output 10 kW / 10 kVA
Input Voltage 380 / 400 / 415 V AC, 3-phase
Output Voltage 380 / 400 / 415 V AC, 3-phase
Frequency Input 40โ€“70 Hz โ€ข Output 50/60 Hz (sync to mains) or 50/60 Hz ยฑ0.1% (free-run)
Input Current (Max/Phase) 18 A
Short-Circuit Withstand (Icw) 65 kA
Power Factor / Cos ฯ† Load PF 0.7 leading to 0.7 lagging (no derating) โ€ข Cos ฯ† 0.99
Harmonics Input THD < 3% (full load) โ€ข Output THD < 1% linear / < 3% non-linear
Bypass Built-in static bypass
Overload Capability 10 min @ 125% โ€ข 60 sec @ 150%
Waveform / Regulation Sine wave โ€ข Output voltage tolerance ยฑ1% after 50 ms
Crest Factor 2.5
Wiring / Connectors Input: Hard-wire 4-wire (3PH + G) or 5-wire (3PH + N + G) โ€ข
Output: Hard-wire 5-wire (3PH + N + G)
Battery (Installed) 1ร— internal 9Ah smart modular battery string
Battery Expansion Expandable up to 4 strings total for increased runtime
Included Service 5ร—8 Start-Up (commissioning support during standard business hours)
Service & coverage

Start-up service is designed to help ensure proper commissioning, parameter setup, and operational verification. Runtime charts are provided in the Documents tab and vary by load and the number of installed battery strings (1โ€“4).

๐Ÿ’ก
Maintenance tip: For best lifecycle performance, size the UPS for growth (headroom) and validate harmonic/load profile during commissioningโ€”especially for non-linear IT loads.
๐Ÿ› ๏ธ
Tech support: Need help confirming 380/400/415 V site compatibility, bypass requirements, or battery string sizing? Email gps@gruber.com.