MGE – Galaxy – 225 KVA – UPS – Refurbished

Manufacturer

OEM Part Number

GLPW225KG

GPS Part Number

GLPW225KG

Price:

$25,971.29

Specifications
View Spec Sheet
Voltage AH/kVA Length Width Height Weight
225 kVA / 202.5 kW 480 VAC 33.66″ 47.83″ 74.80″ 2640 lb
Voltage 225 kVA / 202.5 kW
Amp/H 480 VAC
Length 33.66″
Width 47.83″
Height 74.80″
Weight 2640 lb

Refurbished UPS — MGE Electric Galaxy PW 225 kVA
(GLPW225KG)

480 V 3-phase (3-wire + G) •
True double-conversion (VFI) •
0.9 PF output (202.5 kW) • Tower cabinet

The MGE Galaxy PW 225 kVA is a robust three-phase on-line UPS for medium data centers and industrial facilities.
Our refurbished units are fully reconditioned, cosmetically refreshed, and tested in the USA for reliable,
ready-to-deploy service.

What you get
  • Thorough refurbishment — inspection, OEM-spec wear-part replacement, repaint, final QA
  • Comprehensive testing — burn-in, functional verification, alarms cleared
  • Network-ready — LCD/HMI; SNMP/web, Modbus/RS-485, and relay I/O options
  • Generator-friendly — rectifier walk-in (≈3–10 s) and configurable input power limit
  • U.S. warranty & support from Gruber Power Services

Technical Specifications — Galaxy PW 225 kVA
Category Detail
Power & Topology 225 kVA / 202.5 kW; true double-conversion on-line; efficiency ≈93% at mid-load
Input 480 VAC, 3-phase, 3-wire + G; 60 Hz ±10%; THDi <7.5% at full load; input PF correction up to 0.9 at full load;
configurable input current limit (typ. 360 A); rectifier walk-in to reduce generator inrush
Output 480/208/600 VAC selections (site build); static regulation ±1%; dynamic ±5% @ 100% step; THDU <1% (linear), <4% (non-linear);
overload 125% for 10 min / 150% for 60 s; slew 2 Hz/s (selectable); 0.9 load PF rating
Bypass Integrated static bypass; make-before-break maintenance bypass available in sidecar/panel
Short-Circuit / AIC Up to 65 kAIC available depending on cable-entry/MBP configuration (see OEM drawings)
Battery System External VRLA cabinets; nominal DC bus 480 Vdc (float 545 Vdc; EOD 390 Vdc);
battery current @ full load ≈380 A (max @ EOD ≈547 A); typical recharge ≈12 h; end-cell >1.65 V
Controls & Comm Front LCD/HMI; SNMP/web (IntelliSlot/Unity), RS-485/Modbus, dry-contact relays; EPO/REPO
Physical 74.80″ H Ă— 47.83″ W Ă— 33.66″ D (1900 Ă— 1215 Ă— 855 mm); weight ≈ 2640 lb (1200 kg);
heat dissipation ≈ 48,046 BTU/h; acoustics ≈ 68 dBA @ 1 m
Environment Operating 0–40 °C; ≤95% RH non-condensing; no derate to ~1000 m, then typical capacity derate:
1500–2000 m ≈79%, 2000–2300 m ≈75%, 2300–3000 m ≈69%, 3000–4000 m ≈61%

Battery Cabinets & Options
Accessory Model Notes
External Battery Cabinets Line-up & match (various) Runtime scales by cabinet count & cell selection (480 Vdc plant)
Maintenance/Parallel Bypass External MBP / Parallel Bypass Cabinet Make-before-break service bypass; parallel capacity/redundancy options
Auxiliary / Transformer Cubicle Factory option Input/output isolation or voltage adaptation; distribution sidecar variants
Network / Interface Cards SNMP/Web, RS-485/Modbus, Relay Remote monitoring & alarms; integrates with DCIM/BMS

Notes
  • Specs reflect the 225 kVA (202.5 kW) Galaxy PW 480 V single-module rows; variant I/O voltages and sidecars change some ratings.
  • Confirm final configuration (single/dual-mains, cable entry, MBP/transformer options) on the project cut-sheet and site one-line.

Why buy from Gruber
  • Professionally refurbished — Restored in our electronics engineering lab.
  • Ready to install — Line-up configured to your facility voltage and distribution.
  • Guaranteed quality — Backed by our no-hassle 1-year full replacement warranty.
Gruber Power Services