Protect critical operations with the Liebert 610T 500 kVA / 400 kW UPS, a high-capacity power protection system for data centers and demanding commercial facilities. Its online double-conversion architecture conditions incoming power and supplies regulated, sine-wave output to connected equipment.
Each refurbished system from Gruber Power Services is reconditioned, cosmetically restored, and tested in the USA. Our team helps match the UPS, battery system, bypass arrangement, and monitoring options to your facility’s requirements.
| Category | Details |
|---|---|
| Power & Technology | 500 kVA / 400 kW; online double-conversion with sine-wave output. |
| Input | 480 VAC, three-phase, wye; 60 Hz with a typical 57–63 Hz input window. Rectifier walk-in provides a gradual startup. A 600 V variant may be available; confirm the supplied unit’s configuration. |
| Output | 480 VAC, three-phase; 50/60 Hz, depending on configuration. Nominal full-load output current is approximately 601 A at 480 V, with regulated voltage and fast dynamic response. |
| Bypass | Static bypass, with location and arrangement dependent on system configuration. External wrap-around maintenance bypass equipment is available. |
| Fault Ratings & Protection | Confirm equipment fault ratings and protective-device coordination against the site’s available fault current, electrical one-line, and coordination study. |
| Battery System | External VRLA battery plant with a nominal DC bus of approximately 480 VDC. Maximum battery current at end of discharge is approximately 1,128 ADC for the listed 500 kVA configuration. Module or remote battery disconnect cabinets with 600 VDC-rated breakers are available; final sizing must match the system design. |
| Controls & Monitoring | System control/operator interface, with SCC or SCC-T equipment depending on configuration. Available options include SNMP/web, RS-485/Modbus, dry-contact I/O, and remote emergency power off (REPO) input. |
| Dimensions & Weight | Approximately 97.2 W × 39.0 D × 78.0 H inches (2,469 × 990 × 1,981 mm). Unpacked weight: approximately 9,575 lb (4,343 kg). Confirm dimensions and weight for the supplied configuration before planning delivery and installation. |
| Operating Environment | Recommended ambient temperature: 77°F (25°C). Operation up to 104°F (40°C) without derating; relative humidity up to 95%, non-condensing. Elevations above approximately 4,000 ft may require derating. |
| Option | Details |
|---|---|
| Maintenance Bypass Cabinet | Site-specific MBB equipment provides an external wrap-around bypass path for UPS maintenance and service. |
| System Control Cabinet | SCC / SCC-T equipment provides system control and operator/status functions. Static-switch arrangements depend on the selected system configuration. |
| Battery Plant & Disconnects | Site-engineered VRLA battery cabinets sized for the required load and runtime, with compatible DC disconnect equipment. |
| Communication Interfaces | Compatible network, building-management, and remote-status options, subject to installed hardware and availability. |
Get a professionally refurbished UPS backed by our electronics engineering lab, configuration assistance, and 1-year full replacement warranty.