Manufacturer
OEM Part Number
GPS Part Number
Categories
Tags
| Voltage | WPC | AH/kVA | Length | Width | Height | Weight |
|---|---|---|---|---|---|---|
| 208VAC | N/A | 150 Kva | 34" | 21" | 59" | 640Â lb |
| Voltage | 208VAC |
| WPC | N/A |
| Amp/H | 150 Kva |
| Length | 34" |
| Width | 21" |
| Height | 59" |
| Weight | 640Â lb |
Highly efficient, easy‑to‑deploy 150 kW, 480 V 3‑phase UPS engineered for edge, small/medium data centers, and critical commercial/industrial infrastructure. Designed for external battery systems and includes Start‑Up 5×8 service.
Best‑in‑class power protection with low total cost of ownership — high efficiency, low input distortion, robust short‑circuit withstand, and tight output regulation for sensitive IT and industrial loads.
| Category | Detail |
|---|---|
| Main Input Voltage | 480 V AC, 3‑phase |
| Max Input Current / Phase | 223 A |
| Input Frequency | 40 – 70 Hz |
| Input THD (Full Load) | < 3% |
| Load Power Factor | 0.7 leading to 0.7 lagging (no derating) |
| Efficiency (Full Load) | High‑efficiency operation (spec range: 408…552 V @ 480 V) |
| Output Voltage | 480 V AC, 3‑phase |
| Rated Power | 150 kW / 150 kVA |
| Max Configurable Power | 150 kW / 150 kVA |
| Bypass Type | Built‑in Static Bypass |
| Crest Factor | 2.5 |
| Output Voltage THD | < 1% (linear load) and < 5% (non‑linear load) |
| Output Voltage Tolerance | ±1% after 50 ms |
| Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
| Short Circuit Withstand (Icw) | 65 kA |
Includes Start‑Up 5×8: Deployment/startup service package (5×8 coverage) to help ensure correct commissioning and a clean handoff into production.
External batteries required: Battery cabinets/strings are selected to match your runtime, site constraints, and code requirements.
| Model / Variant | Voltage | Battery Type | Notes |
|---|---|---|---|
| Galaxy VS 150 kW | 480 V 3‑phase | External batteries | Includes Start‑Up 5×8; built‑in static bypass; configurable runtime via external battery system. |
Note: Final configuration (battery cabinet selection, breaker coordination, wiring, and commissioning scope) depends on site requirements and local code. Provide your runtime target and one‑line, and we’ll help align the correct external battery solution.