$349.99
| Voltage | AH/kVA | Length | Width | Height | Weight |
|---|---|---|---|---|---|
| 208 VAC | 4992 VA | 3.5in | 17.48in | 10.00in | 13.93lb |
| Voltage | 208 VAC |
| Amp/H | 4992 VA |
| Length | 3.5in |
| Width | 17.48in |
| Height | 10.00in |
| Weight | 13.93lb |
SKU: PDU-APC-AP7911B Â |
Type: 2U horizontal, Switched rack PDU for 200/208/230Â V single-phase racks (30Â A input). Provides 16Â Ă—Â IECÂ 60320Â C13 outlets with per-outlet on/off control and a local current display; locking NEMAÂ L6-30P input on a 12Â ft (3.66Â m) cord.
| Parameter | Detail |
|---|---|
| PDU Type | Switched; 2U horizontal (rack-mount) |
| Input | 200–240 VAC acceptable; NEMA L6-30P; 1 power cord; length 12 ft (3.66 m) |
| Line Rated / Max Input Current | 24 A line-rated  | 30 A input limit |
| Output Voltage | 208Â VAC (single-phase) |
| Outlets | 16Â Ă—Â IECÂ 60320Â C13 |
| Load Capacity | 4,992 VA (≈5.0 kVA class) |
| Frequency | 50/60Â Hz |
| Dimensions (H Ă— W Ă— D) | 3.50 Ă— 17.48 Ă— 10.00Â in (89 Ă— 444 Ă— 254Â mm) |
| Net Weight | 13.93Â lb (6.32Â kg) |
| Form Factor / Mounting | 2U; rack-mounted; mounting location front or rear; no preference |
| Included Hardware | Rack mounting brackets; installation guide |
| Certifications | ULÂ Listed; cULÂ Listed; CSA; PSE |
| Standards | FCC Part 15 Class A; ICES-003; UL 60950 |
| Environment | Operating: 32–113 °F (0–45 °C), 0–95% RH; Altitude 0–10,000 ft Storage: −13–149 °F (−25–65 °C), 0–95% RH; Altitude 0–50,000 ft |
| Warranty (mfr.) | 2-year repair or replace |
AP7911B is an active NetShelter Switched model with per-outlet control and local current metering. If you need a 120Â V 2U switched alternative, see AP7902B (16Â Ă—Â 5-20R, L5-30P). For 1U 120Â V options, see AP7900B/AP7901B.
| Option | Description | Warranty |
|---|---|---|
| Tested | Operationally verified: L6-30P cord/plug inspection, load checks on all C13 outlets, outlet switching verified, meter readout confirmed. | 90‑Day |
| Refurbished | Cleaned and serviced; cosmetic touch-ups as needed; full outlet and switching re-verification after service. | 1‑Year |
| Model | Input / Plug | Outlets | Rating / Notes |
|---|---|---|---|
| AP7911B | 200/208/230 V 1φ / NEMA L6-30P (12 ft) | 16 × IEC C13 | Switched, 2U; 30 A max; 4,992 VA. |
| AP7902B | 100/120 V 1φ / NEMA L5-30P (12 ft) | 16 × NEMA 5-20R | Switched, 2U; 30 A at 120 V (line-rated 24 A). |
| AP7900B / AP7901B | 120Â V / 5-15P (AP7900B) Â |Â L5-20P (AP7901B) | 8Â Ă—Â 5-15R (AP7900B) Â |Â 8Â Ă—Â 5-20R (AP7901B) | Switched, 1U alternatives for 120Â V racks. |