CARLING-SWITCH – 1-POLE – 15A – DELAY26 – Hydraulic-magnetic circuit breaker – Tested

Manufacturer

OEM Part Number

CA1-B0-26-61-221-K

GPS Part Number

20-CAR-CA1-B0-26-61-221-K

Price:

$14.65

Specifications
View Spec Sheet
Voltage WPC AH/kVA Length Width Height Weight
277 V N/A 15 A 0.8" 1.9" 2.5" 0.11 lb
Voltage 277 V
WPC N/A
Amp/H 15 A
Length 0.8"
Width 1.9"
Height 2.5"
Weight 0.11 lb
Circuit Breaker — Carling Technologies 1-Pole 15A — Delay 26 (Hydraulic-Magnetic)
1-Pole • Hydraulic-Magnetic (Delay 26 — Long) • Tested Reclaimed Part

Genuine Carling C-Series hydraulic-magnetic circuit breaker, cleaned, inspected, and shop-tested. Long-delay “26” curve provides robust motor/high-inrush tolerance with precise, temperature-stable protection.

Where it’s used (typical)
  • AC/DC branch protection for motors, transformers, and controls
  • Industrial/OEM panels, datacom/telecom power
  • Marine/transport and instrumentation requiring tight trip accuracy
At-a-Glance Specs
Parameter Detail
Manufacturer Carling Technologies
Series / style C-Series hydraulic-magnetic, panel-mount
Poles 1 pole (single-pole break)
Current rating (In) 15 A
Voltage ratings 277 V AC (50/60 Hz) • 80 V DC
Delay curve Delay 26 — 50/60 Hz long-delay (holds 100% In; must trip ≥125% In per curve)
Trip technology Hydraulic-magnetic (inverse-time; trip-free; temperature-stable)
Terminations Screw 10-32 back-connect (typ. C-Series); other stud/QC options exist by code
Actuator Handle / toggle (rocker variants available by code)
Mounting Panel mount; 6-32 × 0.195 in threaded inserts (standard rocker bezel)
Dimensions (H × W × D) 63.5 mm × 47.0 mm × 19.18 mm (2.5 in × 1.9 in × 0.8 in)
Weight 0.25 lb (≈ 0.11 kg)
Operating temperature −40 °C to +85 °C
Standards / approvals UL 489 Listed / cULus; IEC/EN 60947-2 (per variant)
Condition Tested pull — cleaned, inspected, verified; light cosmetic wear only
What “Tested Reclaimed Part” Means
  • Visual inspection for heat marks, terminal integrity, and label clarity
  • Mechanical toggle action and latch integrity check
  • Electrical verification: continuity and calibrated trip on Delay 26 curve
Condition, Options & Warranty
Option What’s included Warranty
Tested Pull Cleaned, inspected, Delay-26 function verified; intact labels; ready to install 90-Day