Products

Call Now For Support
1-800-658-5883

12 Volt – 104 Amp Hour YUASA Battery

Manufacturer

OEM Part Number

SWU425-12FR

GPS Part Number

58SSWU425-12FR

Categories

Price:

$300.00

Specifications
View Spec Sheet
Voltage AH/kVA Length Width Height Weight
12 Volt 104 AH 12.01" 6.81" 8.78" 72.53 lbs
Voltage 12 Volt
Amp/H 104 AH
Length 12.01"
Width 6.81"
Height 8.78"
Weight 72.53 lbs
12V 104Ah High-Temperature VRLA AGM Battery
HT X Alloy™ • 10-Year Design Life • UPS & Datacenter Standby Power

The Yuasa SWU425-12FR is a 12-volt, valve-regulated lead-acid (VRLA) battery using absorbed glass mat (AGM)
technology and Yuasa’s high-temperature HT X Alloy™ to deliver long life in demanding standby applications.
With 104 Ah at the 20-hr rate and up to 425 W/cell at 15 minutes (1.67Vpc, 25°C), it provides dependable
short-duration ride-through and robust backup power for UPS systems, datacenters, switchgear, and other critical loads.

The SWU425-12FR features a 10-year design life, flame-arresting one-way vent, epoxy-sealed terminals, and a
flame-retardant UL94V-0 ABS case for enhanced safety in high-density installations. Its maintenance-free,
non-spillable AGM construction meets or exceeds DOT and IATA requirements for non-hazardous transportation, while
top-mounted M6 terminals simplify cabinet and rack installation. Certified to ISO 9001, ISO 14001, and
IEC 60896-21
and recognized by UL, this battery is ready for modern enterprise and industrial environments.

Key Features
  • 12V, 104Ah (20-hr) VRLA AGM battery optimized for high-temperature standby use.
  • High discharge capability — 425 W/cell at 15 minutes (1.67Vpc, 25°C) for strong UPS ride-through performance.
  • 10-year design life with low-capacity loss (~3% per month at 25°C) and rugged ABS case.
  • Flame-retardant construction — UL94V-0 case, flame-arresting one-way vent, and epoxy-sealed terminals.
  • Maintenance-free, non-spillable AGM design suitable for use in enclosed racks and cabinets.
  • Top M6 terminals (torque 4.9 Nm / 43 in-lb) for secure, repeatable connections.
  • Wide operating temperature — discharge from −20°C to 60°C (−4°F to 140°F); operating range −40°C to 65°C (−40°F to 149°F) per manual.
  • Complies with ISO 9001, ISO 14001, IEC 60896-21; UL recognized component (U1989); TAA compliant and DRC conflict-free.
Quick Specs
Parameter Value
Model SWU425-12FR
Nominal Voltage 12 V
Capacity 104 Ah (20-hr rate @ 1.75Vpc, 25°C)
15-min Power 425 W/cell @ 1.67Vpc, 25°C (77°F)
Short-Circuit Current 2135 A
Maximum Charge Current 24.0 A
Internal Resistance 3.0 mΩ
Dimensions (L × W × H over terminal) 305.0 × 173.0 × 223.0 mm (12.01″ × 6.81″ × 8.78″)
Case Height 220.0 mm (8.66″)
Weight 32.9 kg (72.53 lb)
Float Charge Voltage @ 25°C 2.275 ±1% V/cell (temperature compensation −3mV/°C per cell)
Design Life 10 years (standby use)
Typical Applications UPS, datacenter, switchgear & control, energy storage and backup power