$18,885.00
Voltage | AH/kVA | Length | Width | Height | Weight |
---|---|---|---|---|---|
120ย kVA / 108ย kW | 480ย V | 31.6โณ | 31.6" | 73.7" | 1,030ย lb |
Voltage | 120ย kVA / 108ย kW |
Amp/H | 480ย V |
Length | 31.6โณ |
Width | 31.6" |
Height | 73.7" |
Weight | 1,030ย lb |
The Powerware 9390 120ย kVA @ 480ย V is a transformer-free, three-phase online UPS with an integrated static bypass and a variable DC bus.
Our refurbished units are fully reconditioned, cosmetically refreshed, and tested in the USA for dependable, ready-to-deploy service.
Category | Detail |
---|---|
Power & Topology | 120ย kVA / 108ย kW; transformer-free true double-conversion (VFI) with IGBT rectifier & PWM inverter; Hot Syncโข parallel-capable; variable DC bus 432ย Vdc or 480ย Vdc (192โ240 cells). |
Input | Operating input window (3-phase): 480ย V โ 408โ528ย V (nominal +10%/โ15%); frequency range ยฑ5ย Hz of nominal (50/60ย Hz). Input power factor โฅ0.99 (full load); input current distortion โค5% THDi (full load). Rectifier AC input full-load current (conductor sizing): 144ย A @ 480ย V. Line surge withstand: 6ย kV open-circuit / 3ย kA short-circuit. |
Output | Regulation (10โ100% load) ยฑ1%; adjustable nominal ( ยฑ3% ): 480ย V โ 466โ494ย V. Voltage distortion โค1.5% THD (linear) / โค5% THD (non-linear); transient ยฑ5% for 100% step/removal. Frequency ยฑ0.01ย Hz free-running; synchronous to bypass within ยฑ0.5ย Hz; slew โค1ย Hz/s. Full-load output current: 144ย A @ 480ย V. Overload: 110%/10ย min, 125%/30ย s, 150%/10ย s. |
Bypass | Integrated static bypass; permissible window +5% / โ8% of output setting; sync bandwidth ยฑ0.5ย Hz. |
Short-Circuit / AIC | Coordinate breaker/withstand ratings per site one-line and configured lineup (UPS/IAC/IDC). |
Battery System | External Integrated Battery Cabinets (IBC-S / IBC-L); variable DC bus 432โ480ย Vdc at the UPS terminals. DC current at 2.0ย V/cell (end-of-discharge): 302ย Aย dc (120ย kVA). Maximum DC input breaker (continuous duty): 450ย A. |
Controls & Comm | Front LCD/HMI with metering & event log; dual X-Slot bays (web/SNMP, Modbus/RS-485, serial); remote alarm I/O; REPO. |
Physical | UPS cabinet (100โ160ย kVA frame): 73.7″ H ร 35.6″ W ร 31.6″ D (1873 ร 904 ร 804ย mm). Installed weight: 970ย lb (440ย kg). Shipping weight: 1030ย lb (467ย kg). Point loading: 6 points @ 73ย lb each. Heat rejection at full load: 32.8ย kBTU/h (480ย V). Typical exhaust air: ~2000ย cfm. Required clearances: 36″ front, 18″ top. |
Environment | Operating 0โ40ย ยฐC (25ย ยฐC recommended); altitude โค1500ย m at 40ย ยฐC without derating; RH โค95% non-condensing; acoustics ~65ย dB @ 1ย m. |
Accessory | Model | Notes |
---|---|---|
Integrated Battery Cabinet | IBC-S / IBC-L | External runtime cabinets for 9390 (variable 432โ480ย Vdc bus). |
Integrated Accessory Cabinet | IAC-B / IAC-T / IAC-D | Wrap-around maintenance bypass / tie cabinet (matching sidecar). |