Manufacturer
OEM Part Number
GPS Part Number
Categories
Tags
$3,391.25
| Voltage | AH/kVA | Length | Width | Height | Weight |
|---|---|---|---|---|---|
| 480/208/120 | 60Â kVA | 81.0 | 24.0 | 36.0 | ~1400 |
| Voltage | 480/208/120 |
| Amp/H | 60Â kVA |
| Length | 81.0 |
| Width | 24.0 |
| Height | 36.0 |
| Weight | ~1400 |
APC Symmetra PX — PDU Cabinet (60 kVA)
SKU: PDU-APC-SPX60-PDU Â |
Type: Floor-standing Power Distribution Cabinet for Symmetra PX 60Â kVA / 60Â kW line-ups.
Typical electrical path: 480Â V 3-phase input to 120/208Â V 3-phase distribution, with integrated maintenance bypass (MBB) and
dual panelboard branch distribution for downstream racks.
| Parameter | Detail |
|---|---|
| Cabinet Type | Power Distribution Cabinet with integrated Maintenance Bypass (MBB) |
| Compatible UPS | APC Symmetra PX 60Â kVA / 60Â kW systems |
| Input | 480Â V 3-phase, 60Â Hz, hard-wired (top/bottom entry; site-dependent lugs) |
| Output | 120/208Â V 3-phase distribution to branch circuits (panelboards) |
| Frame Rating | 60Â kVA (60Â kW) |
| Nominal Output Current | ≈ 167 A @ 208 V 3ϕ (balanced), for capacity planning |
| Maintenance Bypass | Three-breaker MBB (UPS, Bypass, Tie), mechanically interlocked |
| Distribution | (2) 42-pole panelboards; top and/or bottom cable egress |
| Dimensions (HĂ—WĂ—D) | ~Â 81Â Ă—Â 24Â Ă—Â 36Â in (2057Â Ă—Â 610Â Ă—Â 914Â mm) |
| Approx. Weight | ~Â 1,400Â lb (635Â kg) cabinet-only (varies with options) |
| Approvals | UL / cUL; construction to ULÂ 60950 / equivalent power distribution standards |
| Environment | Operating: 32–104 °F (0–40 °C), 0–95% RH non-condensing; Elevation 0–10,000 ft Storage: 0–113 °F (0–45 °C), 0–95% RH; Elevation 0–30,000 ft |
| Color | Black / dark gray (PX family finish) |
| Warranty (mfr.) | 1-year repair or replace (typical for distribution cabinets) |
Designed to pair with Symmetra PX 60Â kVA frames in 208Â V distribution environments. Alternate builds are commonly available
for 208→208 V (transformer-less) and 600→208 V input schemes with the same 60 kVA frame rating.
Check pole counts, feeder size, and cable entry before ordering.
| Option | Description | Warranty |
|---|---|---|
| Tested | Input/output verification; MBB functional test; breaker operation & interlock checks; panelboard continuity; label & indicator checks. | 90‑Day |
| Refurbished | Cleaned and serviced cabinet; cosmetic touch-ups; torque & insulation tests; full MBB & distribution re-test with report. | 1‑Year |
| Variant | Input → Output | Distribution | Notes |
|---|---|---|---|
| PX60 PDU — 480→208 | 480 V 3ϕ → 120/208 V 3ϕ | (2) 42-pole panelboards | Most common North American configuration; integrated MBB. |
| PX60 PDU — 208→208 | 208 V 3ϕ → 208 V 3ϕ (transformer-less) | Panelboard distribution | Use where 208 V service is available; integrated MBB option. |
| PX60 PDU — 600→208 | 600 V 3ϕ → 120/208 V 3ϕ | Panelboard distribution | Canadian/industrial feed scenarios; integrated MBB. |